Surge Protective Device

  • LT-20, Uc275V, Uc320V, Uc385v,Uc440V. In 10kA, Imax 20kA
  • LT-20, Uc275V, Uc320V, Uc385v,Uc440V. In 10kA, Imax 20kA

LT-20, Uc275V, Uc320V, Uc385v,Uc440V. In 10kA, Imax 20kA

It is mainly used to provide T2 protection for various electronic and electrical equipment in buildings vulnerable to lightning overvoltage.Mainly used as primary protection equipment in the main distribution system.

Characteristic

Location of Use:Distribution cabinet,JP cabinet etc.
Network Systems:TN-S,TN-C,TT
Mode of Protection:L-PE,N-PE,L-PEN,L-N
Protective Elements:High Energy MOV

Chinese Standard:GB/T18802.11-2020
IEC standard:IEC 61643-11:2011
European standard:EN 61643-11:2012
Certificates:TUV,CE,CQC

Technical Data

Model numberLT-20LT-40
Max Continuous Operating VoltageUc(V~)275/320/385/440275/320/385/440
Nominal discharge currentIn(kA)1020
Maximum discharge currentlmax(kA)2040
Protection levelUp(kv)<1.3/1.4/1.6/1.8<1.4/1.5/1.8/2.2
Response time(ns)<25<25
General parameter   
Access wire area(mm²)≥10≥10
Access ground cross-sectional area(mm²)≥16≥16
SPD special disconnectorRecommendLT-SSD40LT-SSD40
Working environment-40~+70°C,relative humidity<95%(below 25℃)
Remote communication connection       1411:NO,1112:NC
Associated disconnectors
Thermal disconnector internal

Mechnical characteristics

Connection By screw terminals6-25  mm²
Terminal Screw Torque2.5 Nm
Recommended Cable cross Section≥16mm²
Insert wire length15mm
Mounting DIN rail35mm(EN60715)
Degree of ProtectionIP20
HousingPBT/PA
Flame retardant gradeUL94 V0
Operating temperature-40℃~+70℃
Operating relative humidity5%-95%
Working atmospheric pressure70kPa~106kPa

Size

Poles1P1+NPE2P3P4P3+NPE
Size (mm)18×90(83)×6736×90(83)×6736×90(83)×6754×90(83)×6772×90(83)×6772×90(83)×67
Packing Inner box
Delivery packaging Carton or Pallet

Dimensional drawing