Surge Protective Device

  • YH10W-110KV Surge Arrester In Substation
  • YH10W-110KV Surge Arrester In Substation

YH10W-110KV Surge Arrester In Substation

The electrical equipment used by the Zinc Oxide lightning arrester to protect the AC power system is protected from overvoltage and overvoltage damage.

Use characteristics

  The Zinc Oxide lightning arrester is the most advanced over-voltage protector in the world. Because its core component resistors are made of Zinc Oxide and various metal oxides, compared with traditional silicon carbide arresters, it greatly improves the volt ampere characteristics of resistors, improves the capacity of resistors, and brings about the fundamental change of the characteristics of arresters.

     When the lightning arrester under normal operating voltage, the current flow through the arrester only microamp level when subjected to voltage, non linear volt ampere characteristics of arrester excellent function, current flow through the arrester moment increased to several thousand amperes, lightning arrester in the conducting state, the release of piezoelectric energy, so as to effectively limit over against the voltage of power transmission equipment.

Conditions of use

The temperature of the environment is not higher than +40℃, not less than -40℃
The altitude is not more than 1000 (the plateau should be marked at the time of order).
The frequency of the power supply is not less than 48Hz, not more than 60Hz.
The power frequency voltage applied to the arrester for a long time does not exceed the continuous operating voltage of the arrester.
The maximum wind speed is not more than 35m/s;
The earthquake intensity is 7 degrees and below.
Mark the stain area.
 

Technical performance

The performance of the products can meet the requirements of GB 11032-2000, JB/T8952-2005, JB/T10497-2005 and DL/T815-2002.

Model description

technical parameter

ModelRated voltageSystem nominal voltageContinuous operating voltageDC (U1mA) reference voltageMaximum residual pressure KV (peak value)2000us square wave current (peak value)4/10us impact current (peak value)0.75U1mA DC reference voltage
Maximum leakage current
Shock current of steep slopeLightning stroke currentOperating shock current
YH10WZ-100/2601001107814529126022160010050
YH10WZ-102/2261021107906148291266226
YH10WZ-108/28110811084157315281239

Shape size